What is the difference between an MDB and a motor control panel (MCC)?
An MDB (Main Distribution Board) is the main panel that takes power from the transformer or utility meter and distributes it to the sub-panels in a building. It holds the main breaker, a power meter and a breaker for each circuit.
A motor control panel (MCC) starts, stops and protects motors such as water pumps, fans and aerators. Inside are contactors, overloads, phase protection relays and control switches.
Most of the panels we build are MCCs for clean water, wastewater and stormwater systems, as well as building automation systems. We use standard components and tidy wiring for safe operation.
- MDBDistributes the building main supply, splits circuits and meters total energy use
- MCCRuns and protects motors, pumps, fans and other equipment
DOL, star-delta or inverter: which motor starter should I choose?
It depends on the motor size and how it is used. This is our rule of thumb, which we then confirm on site.
Float switch or level sensor: which is better for pump control?

Electric float switches suit sumps, water tanks and ordinary wastewater pits. They are cheap, easy to repair and site staff can replace them. The pump starts and stops at the levels you set.
If you want to see the water level as a number on your phone or computer, or let a PLC act on several levels, we recommend a level sensor such as 4-20mA or RS-485 wired to a PLC. It can control the pumps precisely and can later be extended to online monitoring.
Our pump control panels are designed to work with both float switches and sensors, and include an alternating function to extend the life of the pumps.
Engineer’s tip: In wastewater pits with debris, floats often get tangled. Fit a guard pipe or screen, and check the floats on every PM visit.
What is the difference between indoor and outdoor control panels?
Indoor panels focus on cooling, dust and insect protection, and preventing accidental contact with live circuits. Outdoor panels are designed to withstand sun, rain and water ingress. If the panel is outdoors and exposed to rain, we recommend a roofed or double-door enclosure to prevent water pooling and long-term leakage. For very humid or chemical environments, or where extra durability is needed, we recommend stainless steel.
We design and select enclosures to suit the site, using popular brands such as Denco, Tamco, BAV and KJL. We use a hydraulic punch to cut holes for lights and switches, leaving a smooth finish with no metal burrs that could damage the seals. For special sizes we order from a factory that can laser-cut holes to your specifications.
- Single-door enclosure with ventilation Indoors and pump rooms: protects against dust and some splashing
- Double-door enclosure with glass front door Outdoors, wastewater treatment areas and rooftops
- Stainless steel enclosure Very damp or chemical areas, such as wastewater treatment systems that use chemicals
Why does my panel trip, the pump not run, or the motor overload?
The causes we see most often are: the pump bearings are stuck or drawing too much current, low voltage or a missing phase, moisture inside the panel causing terminals to rust, and components wearing out with age. Panels without a phase protection relay are more likely to damage the motor. Another common cause of motor and magnetic breaker failure is resetting the overload and continuing to run the pump without finding the cause first.
We repair and troubleshoot existing panels, including those built by others. We check the wiring, improve the circuit, replace components and repaint the panel so it works normally and safely again.
Engineer’s tip: Why does a 3-phase motor burn out when a phase is missing? If only one phase reaches the motor, it will not be damaged. But when two phases reach it, the voltage across the windings becomes very high and burns them out. A protection device should make sure all three phases are supplied fully and in balance.
Why does a control panel use so many wire colours, and which standard do they follow?
Different wire colours tell the different lines and circuits apart, prevent wires from being connected the wrong way round, and help electricians work safely. Today, wire colours follow the international IEC standard (and the new Thai TIS standard).
We use wire colours according to IEC 60204-1, as follows:
- Black AC and DC power circuits
- Red AC control circuits
- Blue DC control circuits
- Orange External circuits that are not switched off from inside the panel
Engineer’s tip: Some sites use wire colours from other standards. Always check the drawings or measure the voltage before working.
Popular panels with starting prices
Prices are starting prices for the panel only and exclude on-site cabling and installation.

3-phase control panel for two water pumps, alternating and assist operation, 4-level float switch control
For drainage pumping. The pumps alternate to extend their life. If one fails, the other takes over automatically, and if the water gets very high both run together. High level alarm included.
- Components
- Schneider Electric (MCB, Contactor, Overload, Relay)
- Enclosure
- Steel, outdoor
- Control
- DOL starter, float switch control · Auto / Off / Manual
- Protection
- Thermal overload, phase protection

Single-phase control panel for two water pumps, alternating and assist operation, 4-level float switch control
For drainage pumping. The pumps alternate to extend their life. If one fails, the other takes over automatically, and if the water gets very high both run together. High level alarm included.
- Components
- Mitsubishi (Contactor, Overload) + Eaton (MCB) + Lanboo (Relay)
- Enclosure
- Steel, outdoor
- Control
- DOL starter, float switch control · Auto / Off / Manual
- Protection
- Thermal overload, phase protection

PLC control panel with HMI screen and IoT gateway
For building an online monitoring system using the free cloud that comes with the devices.
- Components
- PLC, HMI, IoT Gateway / HMI with Gateway Haiwell
- Enclosure
- Steel, single-door with 3-inch ventilation fan
- Control
- Programmable with free software: Haiwell Happy (PLC), Haiwell Cloud Scada Designer (HMI, Gateway)
- Comms
- Ethernet, Modbus RTU/TCP, RS-232, RS-485, MQTT

Wastewater treatment motor control panel: wastewater pumps, aerators, return sludge pumps and effluent pumps
One panel controls all the pumps and aerators in the system, with timed start and stop. Works with any system, such as AS or SBR, in malls, fuel stations and hospitals.
- Components
- Per customer spec
- Enclosure
- Per customer spec
- Control
- As required, e.g. float switch + timer · power fault alarm
- Starter
- DOL, Star-Delta, VSD and others, per motor size

Motor control panel with PLC and HMI
For factories or buildings that want to see status on a screen, log power consumption and extend to online monitoring viewable on a phone.
- Components
- Per customer spec
- PLC / HMI
- Per customer spec
- Enclosure
- Per customer spec
- Control
- As required, e.g. 4-20mA level sensor
- Comms
- As required, e.g. Modbus RTU → power meter
Breaker, contactor, overload and cable size calculator
For one motor started direct-on-line (DOL). Enter the nameplate current, or just the motor size if there is no nameplate, and get the equipment and cable sizes straight away.
If the nameplate shows two values, e.g. 220/380V 26/15 A, use the one for the voltage you connect (380V = 15 A).
- Power in kW or HP: goes in Motor power
- Voltage: take the one you actually connect (380V, star / Y)
- The current in the same position as that voltage (15.2 A): goes in the full-load current
- Power factor (cos φ): not needed here, but most nameplates show it
- Circuit breaker (MCCB / MCB)
- Magnetic contactor (AC-3)
- Use the AC-3 current in the catalogue, not the number in the model name: e.g. 18 A is Schneider LC1D18 but Mitsubishi S-T20
- Overload relay
- Main / outside panel
- To the motor
- Inside the panel
- Earth
- green or green/yellow
Based on the Thai electrical installation code (EIT) for direct-on-line starting · Cables are PVC in conduit at 40°C ambient, without voltage drop: long runs, grouped circuits or hot locations need larger cables · Ratings vary by brand; use these as a first estimate and have an electrical engineer check before installing.
What affects the price of a control panel?
- Motor size (kW/HP)Larger motors need different components and starters
- Component brandMitsubishi, Schneider, Siemens and other leading brands
- Enclosure and IP ratingPainted steel or stainless, indoor or outdoor, standard size or custom-made
- FunctionOperating functions and control method